Installation Instructions
Direct Bury Lug

DB Lug Figure 1

DB Lug Figure 2

IMPORTANT: Turn off power before installing or removing connector. Product to be used in accordance with local and national codes.

  1. Strip main and tap conductor(s) to 5/8 inch (width of lug).
  2. Place stripped conductor(s) into side A or B.**
  3. Torque to 35 lb-in.
  4. Repeat steps 1 through 3 for adjacent side.
  5. Remove sealant cover and discard.
  6. Close housing, aligning conductors until housing lid is fully latched.
  7. Do not reuse.

**Use side A for uncut main or tap conductors (Figure 1). When splicing multiple tap conductors on side A or B use only like gauge and type (solid/stranded). Do not install multiple conductors into the same lug opening (Figure 2).
Side A
(1 Main or 1-2 Tap) #14 - 10 Solid and Stranded Copper
(1 Main or 1-2 Tap) #14 - 10 Solid and Stranded Copper Tracer Wire
(1 Main or 1-2 Tap) #12 Steel Core Tracer Wire (380 and 1200 pound)
Side B
(1-2 Tap) #14 - 10 Solid and Stranded Copper
(1-2 Tap) #14 - 10 Solid and Stranded Copper Tracer Wire
(1-2 Tap) #12 Steel Core Tracer Wire (380 and 1200 pound)